Full-scale simulation and safety analysis of leakage and dispersion in large-scale liquid hydrogen storage areas
Journal of Tsinghua University (Science and Technology) 2026, 66(3): 440-451
Published: 10 April 2026
Abstract PDF (13.6 MB) Collect
Downloads:5
Objective

Although liquid hydrogen provides high energy density and clean combustion, it poses significant safety risks due to its low boiling point, high diffusivity, and flammability. Therefore, addressing the safety challenges associated with large-scale liquid hydrogen leaks is essential for operational safety and risk management in hydrogen infrastructure, particularly in large-scale storage areas. This study investigates the dispersion characteristics of hydrogen vapor clouds and subsequent fire hazards following catastrophic leakage events, providing critical insights into safety implications under diverse environmental conditions.

Methods

A numerical model based on the fire dynamics simulator (FDS)—an advanced computational fluid dynamics tool developed by the U.S. National Institute of Standards and Technology—was developed. The applicability and accuracy of FDS in hydrogen safety simulations were systematically validated through comparisons with experimental data, quantitative error analysis, and cross-validation using peer studies. The simulations examined leakage scenarios involving evaporation, vapor dispersion, and fire development, incorporating fluid dynamics, phase change, combustion, and thermal radiation processes. Environmental factors such as overhead obstructions and solar radiation were also considered. The leakage source was modeled as a liquid hydrogen storage tank located at the center of a large-scale storage area. The lateral dispersion behavior of the hydrogen cloud under varying wind speeds and its impact on structures located off the downwind direction were analyzed. Subsequently, three comparative scenarios were established: a baseline case, a case with overhead confinement, and one with solar radiation. The effects of ceiling obstructions and solar heating on hazardous exposure times and cloud dispersion were evaluated. Moreover, the fire development and potential hazards in the vicinity of the storage area following immediate ignition after leakage were examined.

Results

Simulation results indicated that: (1) Buildings located offset from the main wind direction were not affected by the lateral dispersion of the flammable hydrogen cloud. (2) The ceiling structure suppressed the vertical dispersion of the hydrogen cloud during the initial leakage phase and increased the horizontal transport rate, leading to a large gas-to-ground contact area and a prolonged hazardous exposure duration in near-field regions, which resulted in an increase in hazardous exposure time at Building 2 by 5s. (3) Solar radiation played a minimal role in the early-stage evaporation and dispersion of liquid hydrogen. Its thermal effect grew with time, serving to prolong the hazardous exposure time at building facility 2 by 12 s through accelerated cloud dispersion, with a corresponding delay in far-field arrival due to enhanced dilution. (4) In the event of ignition, the liquid hydrogen fire developed extremely rapidly, reaching a flame height of 30m and a lateral spread of 15 m within 9s; the core flame temperature exceeded 700℃. In the simulated fire scenario, the thermal radiation intensity in the ceiling monitoring area consistently exceeded the safety threshold. The thermal radiation intensity exceeded 12.5kW/m2, accounting for over 70% of the total simulation time, potentially causing structural damage such as steel failure and concrete spalling.

Conclusions

Quantitative studies on overhead confinement and solar radiation provide new insights into the potential risks of hydrogen facilities in complex environments, while research on the dynamic characteristics of accidental fires offers valuable information for the prevention of daily fires and the development of appropriate strategies to suppress fires.

Research Article Issue
Particulate matter emission by an isolated rotating wheel
Building Simulation 2021, 14(4): 1163-1173
Published: 21 October 2020
Abstract PDF (559 KB) Collect
Downloads:84

Particulate matter emission from rotating wheels, which imparts a force to the contact surface and causes strong air currents, is one of the important pollutant sources on the road. This study investigates the particulate matter emission by measuring mass and size distributions of particulate matter near an isolated rotating wheel in a deliberately designed setup. Five rotating speeds from 0.7 m/s to 1.5 m/s are conducted to test its impact on the emission of particulate matter. Mass of particulate matter is measured at twenty-six sampling points around the rotating wheel under different experimental conditions. Experimental results show that the farther away from the wheel, the less of particulate matters deposited on the sampling points in general. Moreover, the emission factor increases from 0.12 g/vkt to 0.24 g/vkt when the rotating speed of the wheel increases from 0.7 m/s to 1.5 m/s. The number and proportion of PM2.5 and PM10 on different sampling points are also measured. The results show that the position of the highest number of PM2.5 and PM10 tends to move to a further and higher sampling point with the increasing of the speed. Moreover, the number proportions of PM2.5 and PM10 on the sampling points range from 19% to 97% and 61% to 100% at different speeds, respectively. This study is believed to be helpful to estimate particulate matter emission and make effective control strategies on targeted pollution.

Research Article Issue
A novel circulated air curtain system to confine the transmission of exhaled contaminants: A numerical and experimental investigation
Building Simulation 2020, 13(6): 1425-1437
Published: 04 August 2020
Abstract PDF (959.8 KB) Collect
Downloads:104

Air curtain is an efficient device for cutting off airflow and confining contaminants. Inspired by the ability, a circulated air curtain composed of end-to-end plane jets generated by a relay of air pillars is proposed to confine exhaled contaminants in this study. Furthermore, the optimization study of computational fluid dynamics (CFD) is conducted to explore cutting-off performance and find better design parameters under different conditions, i.e., human-curtain distance, enclosure shape, jet velocity from air pillar, and exhalation modes. The multidirectional blockage and vortex-like rotative transmission routes of exhaled airflow are observed when air curtain exists. Results indicate that contaminants are concentrated around the source. The average mole fraction of exhaled contaminants outside air curtain under different human-curtain distance decreases 4.3%-19.6% compared to mixing ventilation with same flux. Shortening the human-curtain distance can improve the performance of air curtain and may change the direction of exhaled airflow. Moreover, It has better performance when the enclosure shape is close to a circle. Higher jet velocity is better for improving the confinement performance, but the trend is not very obvious as velocity increases. For exhalation modes, it is more challenging to control exhaled contaminants for intense exhalation activity (such as coughing) in steady simulation, but results in transient simulation show better performance when coughing only once. These results can provide a reference for the subsequent design and improvement in applying air curtain in hospital wards or other places, especially during the period of flu outbreak.

Research Article Issue
Using air curtains to reduce short-range infection risk in consulting ward: A numerical investigation
Building Simulation 2021, 14(2): 325-335
Published: 26 June 2020
Abstract PDF (912.9 KB) Collect
Downloads:106

Air curtains is promising in reducing the short-range infection risk in hospitals. To quantitatively evaluate its performance, this paper explores air curtains equipped on normal consulting desk to avoid doctor’s direct exposure to the patient exhaled pollutants. A numerical investigation is conducted to evaluate the effects of supply air velocity and angle on cutting off performance. Simulation results show that the average mass fraction of exhaled pollutants decreases significantly (70%-90%) in the consulting ward, indicating satisfying performance of air curtains. Increasing supply air velocity is demonstrated to be conducive in forming full air curtains, whereas an excessively high supply air velocity may be of adverse effects by entraining exhaled flow. Besides, the supply air angle is also critical due to its coupling with supply air velocity. It is found that larger angle (0°-40°) is better where velocity is less than 3 m/s, otherwise a small angle (20°) is preferable where velocity is larger than 3 m/s. Exhaled flow could be well suppressed at the supply air angle 20° but moves over air curtains at 40°. This study can provide effective and intuitive guidance in applying air curtains in consulting wards.