Research Article

Optimization of indoor environmental quality and ventilation load in office space by multilevel coupling of building energy simulation and computational fluid dynamics

Yunqing Fan, Kazuhide Ito( )
Interdisciplinary Graduate School of Engineering Science, Kyushu University, 6-1 Kasuga-koen, Kasuga, Fukuoka 816-8580, Japan
Show Author Information

Abstract

The fundamentals, implementation, and application of an integrated simulation as an approach for predicting the indoor environmental quality for an open-type office and for quantifying energy saving potential under optimized ventilation are presented in this paper. An integrated simulation procedure based on a building energy simulation and computational fluid dynamics, incorporated with a conceptual model of a CO2 demand controlled ventilation (DCV) system and proportional integral control of an air conditioning system as the optimization assessment of conceptual model in the occupied zone, was developed. This numerical model quantitatively exhibits energy conservation and represents the non-uniform distribution patterns of airflow properties and CO2 concentration levels in terms of energy recovery and indoor thermal comfort. By means of an integrated simulation, the long-term energy consumption of heating, ventilation, and air conditioning systems are predicted precisely and dynamically. Relative to a ventilation system with a basic constant air volume supply rate characterized by a fixed outdoor air intake rate from the ceiling supply opening, the optimized CO2-DCV system coupled with energy recovery ventilators reduced total energy consumption by 29.1% (in summer conditions) and 40.9% (winter).

References

【1】
【1】
 
 
Building Simulation
Pages 649-659

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Fan Y, Ito K. Optimization of indoor environmental quality and ventilation load in office space by multilevel coupling of building energy simulation and computational fluid dynamics. Building Simulation, 2014, 7(6): 649-659. https://doi.org/10.1007/s12273-014-0178-3

1327

Views

25

Crossref

N/A

Web of Science

25

Scopus

0

CSCD

Received: 29 October 2013
Revised: 23 January 2014
Accepted: 03 February 2014
Published: 05 April 2014
© Tsinghua University Press and Springer-Verlag Berlin Heidelberg 2014