The amplitude of switching overvoltages is a key factor for designing the insulation of UHV equipment. The effect of different arresters needs to be studied, since installing arresters is an important way to suppress switching overvoltages in UHV transmission lines. Switching overvoltages on the 1000 kV Huainan-Huxi double-circuit transmission line were simulated for different operating modes and different arrester designs using the electromagnetic transient program PSCAD/EMTDC. With parallel resistors, the switching overvoltages are less than 1.70 p.u. (1.0 p.u.=1100×