Grid-forming (GFM) control is a key technique for power systems with high penetration of converter-interfaced generation. However, its application to photovoltaic (PV) systems faces challenges related to DC voltage transient stability. This paper investigates a common countermeasure involving a PI-based DC voltage controller for GFM-PV systems, revealing that their small-signal stability is sensitive to parameter tuning. The study develops a generalized DC voltage-dominated 2nd-order GFM model and successfully conducts complex torque analysis, showing that this approach can be effectively extended to other dynamics governed by DC voltage-dominated GFM systems. Subsequently, the paper establishes a stability criterion for GFM-PV systems and proposes a parameter tuning method for DC voltage controllers that incorporates damping margin considerations. The performance of the tuned single-machine-infinite-bus GFM-PV system is validated on the RT-LAB real-time simulation platform under scenarios involving solar irradiance fluctuations and grid frequency disturbances. The proposed method proves effective in ensuring the stability of the GFM-PV system, with robust theoretical support.
- Article type
- Year
Open Access
Special Section Paper
Issue
Open Access
Article
Issue
Grid-forming (GFM) control is a key technology for ensuring the safe and stable operation of renewable power systems dominated by converter-interfaced generation (CIG), including wind power, photovoltaic, and battery energy storage. In this paper, we challenge the traditional approach of emulating a synchronous generator by proposing a frequency-fixed GFM control strategy. The CIG endeavors to regulate itself as a constant voltage source without control dynamics due to its capability limitation, denoted as the frequency-fixed zone. With the proposed strategy, the system frequency is almost always fixed at its rated value, achieving system active power balance independent of frequency, and intentional power flow adjustments are implemented through direct phase angle control. This approach significantly reduces the frequency dynamics and safety issues associated with frequency variations. Furthermore, synchronization dynamics are significantly diminished, and synchronization stability is enhanced. The proposed strategy has the potential to realize a renewable power system with a fixed frequency and robust stability.
Open Access
Regular Paper
Issue
It is essential to study large-disturbance stability of power systems with high proportion of power electronic devices to discover new instability modes of renewable energy generation connected to the grid. In this paper, a model of power system with synchronous generator (SG) and voltage source converter (VSC) interfaced wind power generation is built, and time-domain simulations of the system under large disturbances are carried out for two cases in which the proportion of wind power is small and large, respectively. When wind power takes up a small proportion, instability mode of the system is rotor angle instability dominated by the SG. When wind power takes up a large proportion, instability is caused by outer control loop. The mechanism of new instability mode introduced in the wind power control link is analyzed from the angle of voltage limit and power limit. In addition, this paper studies the effect of low-voltage ride through (LVRT) switching strategy. Through comparison of simulations, it is verified different switching control strategies may correspond to different fault critical clearing time, i.e. different large-disturbance stability.
With the large-scale access of new energy to the power grid, the inertia of the power system gradually decreases, and the system frequency security is seriously threatened. In this study, "critical inertia" is used to quantify the minimum inertia required to maintain system stability after a critical failure. First, an analytical frequency safety calculation method is proposed. By constructing the frequency difference curve, the calculation formula of the frequency safety constraint is obtained based on the average system open-loop model. Then, based on the frequency safety constraint, the rate of change of frequency constraint (RoCoF), and the unit regulation power constraint, the calculation of the system-critical inertia is transformed into the solution of the optimization problem. Finally, the simulation system is used to verify the effectiveness and accuracy of the critical inertia calculation method in this study. The simulation results show that the larger the adjustable power range of the unit is, the smaller the critical inertia becomes. By increasing the standby capacity of the unit, the critical inertia of the system can be reduced.
京公网安备11010802044758号