Large-disturbance Instability Modes of Power System with Synchronous Generator and VSC Interfaced Generation

Liangshuai Hao1, Lei Chen1( ), Yong Min1, Yalou Li2, Shiyun Xu2
Department of Electrical Engineering, Tsinghua University, Beijing 100084, China
China Electric Power Research Institute, Beijing 100192, China
Show Author Information

Abstract

It is essential to study large-disturbance stability of power systems with high proportion of power electronic devices to discover new instability modes of renewable energy generation connected to the grid. In this paper, a model of power system with synchronous generator (SG) and voltage source converter (VSC) interfaced wind power generation is built, and time-domain simulations of the system under large disturbances are carried out for two cases in which the proportion of wind power is small and large, respectively. When wind power takes up a small proportion, instability mode of the system is rotor angle instability dominated by the SG. When wind power takes up a large proportion, instability is caused by outer control loop. The mechanism of new instability mode introduced in the wind power control link is analyzed from the angle of voltage limit and power limit. In addition, this paper studies the effect of low-voltage ride through (LVRT) switching strategy. Through comparison of simulations, it is verified different switching control strategies may correspond to different fault critical clearing time, i.e. different large-disturbance stability.

References

【1】
【1】
 
 
CSEE Journal of Power and Energy Systems
Pages 1481-1488

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Hao L, Chen L, Min Y, et al. Large-disturbance Instability Modes of Power System with Synchronous Generator and VSC Interfaced Generation. CSEE Journal of Power and Energy Systems, 2025, 11(4): 1481-1488. https://doi.org/10.17775/CSEEJPES.2022.02320