Geothermal-integrated thermally anisotropic building envelope for energy and peak-demand reduction

Daniel Howard, Zhenglai Shen, Diana Hun, Som Shrestha( )
Buildings and Transportation Science Division, Oak Ridge National Laboratory, P.O. Box 2008, Oak Ridge, TN 37831, USA
Show Author Information

Abstract

Buildings consume large amounts of energy for heating and cooling, while peak electricity demand places significant stress on the power grid. This paper presents a reduced-order co-simulation framework and load-oriented supervisory control strategy for a geothermal-integrated thermally anisotropic building envelope with a ground loop (TABE+GL). In TABE+GL, a hydronic loop embedded in the building envelope is directly coupled with a geothermal ground loop, allowing for bidirectional heat exchange between the envelope, the ground, and the indoor environment. A hybrid co-simulation framework was established by coupling a reduced-order resistor–capacitor (RC) thermal network model with EnergyPlus augmented with GHEDesigner modules. The RC model generated feasible heat flux options under three operating modes, and EnergyPlus predicted sensible loads, energy use, and pump energy demand. At each simulation step, a supervisory control algorithm selected the optimal loop configuration and duty factor that maximizes useful TABE geothermal utilization without exceeding the predicted sensible load, thereby avoiding overheating or cooling. Case studies were conducted for Los Angeles, California, Charleston, South Carolina, and Denver, Colorado. Results showed that the proposed framework reduced HVAC electricity consumption by 43%–67%, natural gas use for space heating by 11%–38%, and peak electricity demand by 43%–88%. These results highlight the potential of combining reduced-order envelope modeling, direct geothermal coupling, and load-oriented supervisory control to improve whole building energy performance and reduce peak demand across diverse weather conditions.

References

【1】
【1】
 
 
Building Simulation
Pages 2169-2184

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Howard D, Shen Z, Hun D, et al. Geothermal-integrated thermally anisotropic building envelope for energy and peak-demand reduction. Building Simulation, 2026, 19(8): 2169-2184. https://doi.org/10.1007/s12273-026-1478-0

3

Views

0

Crossref

0

Web of Science

0

Scopus

0

CSCD

Received: 06 April 2026
Revised: 11 June 2026
Accepted: 30 June 2026
Published: 15 August 2026
© UT-Battelle, LLC and Daniel Howard, under exclusive licence to Tsinghua University Press 2026