Research Article

Optimization of data center thermal management performance under failure mode of rack-level heat pipe backplane system

Zichen Lu1, Yanqiang Di1,2( ), Haiyan Di1, Xiaoping Li1, Zhenyu Chen2, Chen Zhao1, Yafeng Gao2
China Academy of Building Research, Beijing 100013, China
Chongqing University, Chongqing 400044, China
Show Author Information

Abstract

To address localized hotspot issues arising from traditional cooling methods in high-power-density data centers and to ensure a stable thermal environment, this study developed a numerical model of a rack equipped with a heat pipe backplane, validated through experimental data. The study evaluated the thermal management performance and fault tolerance of the heat pipe backplane system for data centers under different load rates (60%, 100%) and failure modes (single rack, multiple racks). Results indicate that under a 60% load rate, the rack inlet temperature remained stable between 23.4 and 25.1 ℃, while server outlet temperatures ranged from 27.3 to 32.1 ℃. In the event of a single rack fan group failure, increasing the airflow of adjacent fans by 60% reduced the average rack outlet temperature to below 26.4 ℃. For multiple rack backplane system failures, maintaining appropriate spacing between failed racks kept the overall room temperature below 27 ℃, thereby preventing localized hotspots. However, simultaneous failures of adjacent racks increased the maximum inlet temperature to 27.4 ℃, heightening hotspot risks. These findings demonstrate that heat pipe backplane systems offer significant advantages in optimizing internal rack airflow organization, mitigating hotspot risks, and enhancing fault tolerance, thereby providing crucial theoretical support for the design and optimization of thermal management strategies in data center environments.

References

【1】
【1】
 
 
Building Simulation
Pages 1377-1392

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Lu Z, Di Y, Di H, et al. Optimization of data center thermal management performance under failure mode of rack-level heat pipe backplane system. Building Simulation, 2025, 18(6): 1377-1392. https://doi.org/10.1007/s12273-025-1271-5

1020

Views

6

Crossref

3

Web of Science

3

Scopus

0

CSCD

Received: 16 January 2025
Revised: 27 February 2025
Accepted: 13 March 2025
Published: 26 April 2025
© Tsinghua University Press 2025