Research Article

Development of a Bayesian inference model for assessing ventilation condition based on CO2 meters in primary schools

Danlin Hou1Liangzhu (Leon) Wang1( )Ali Katal1Shujie Yan1Liang (Grace) Zhou2Vicky Wang2Mark Vuotari2Ethan Li1Zihan Xie1
Centre for Zero Energy Building Studies, Department of Building, Civil and Environmental Engineering, Concordia University, 1455 de Maisonneuve Blvd. West, Montreal, Quebec, H3G 1M8, Canada
Construction Research Centre, Engineering Division, National Research Council of Canada, M-24, 1200 Montreal Road, Ottawa, Ontario K1A 0R6, Canada
Show Author Information

Abstract

Outdoor fresh air ventilation plays a significant role in reducing airborne transmission of diseases in indoor spaces. School classrooms are considerably challenged during the COVID-19 pandemic because of the increasing need for in-person education, untimely and incompleted vaccinations, high occupancy density, and uncertain ventilation conditions. Many schools started to use CO2 meters to indicate air quality, but how to interpret the data remains unclear. Many uncertainties are also involved, including manual readings, student numbers and schedules, uncertain CO2 generation rates, and variable indoor and ambient conditions. This study proposed a Bayesian inference approach with sensitivity analysis to understand CO2 readings in four primary schools by identifying uncertainties and calibrating key parameters. The outdoor ventilation rate, CO2 generation rate, and occupancy level were identified as the top sensitive parameters for indoor CO2 levels. The occupancy schedule becomes critical when the CO2 data are limited, whereas a 15-min measurement interval could capture dynamic CO2 profiles well even without the occupancy information. Hourly CO2 recording should be avoided because it failed to capture peak values and overestimated the ventilation rates. For the four primary school rooms, the calibrated ventilation rate with a 95% confidence level for fall condition is 1.96±0.31 ACH for Room #1 (165 m3 and 20 occupancies) with mechanical ventilation, and for the rest of the naturally ventilated rooms, it is 0.40±0.08 ACH for Room #2 (236 m3 and 21 occupancies), 0.30±0.04 or 0.79±0.06 ACH depending on occupancy schedules for Room #3 (236 m3 and 19 occupancies), 0.40±0.32, 0.48±0.37, 0.72±0.39 ACH for Room #4 (231 m3 and 8–9 occupancies) for three consecutive days.

References

【1】
【1】
 
 
Building Simulation
Pages 133-149

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Hou D, Wang L(, Katal A, et al. Development of a Bayesian inference model for assessing ventilation condition based on CO2 meters in primary schools. Building Simulation, 2023, 16(1): 133-149. https://doi.org/10.1007/s12273-022-0926-8

1001

Views

15

Crossref

11

Web of Science

13

Scopus

0

CSCD

Received: 22 March 2022
Revised: 11 July 2022
Accepted: 31 July 2022
Published: 23 August 2022
© Tsinghua University Press 2022