Research Article

Energy-saving and economic analysis of passive radiative sky cooling for telecommunication base station in China

Zengkai Cui1Chenyue Guo1Dongliang Zhao1,2( )
School of Energy and Environment, Southeast University, Nanjing 210096, China
Engineering Research Center of Building Equipment, Energy, and Environment, Ministry of Education, China
Show Author Information

Abstract

The widespread application of 4G and the rapid development of 5G technologies dramatically increase the energy consumption of telecommunication base station (TBS). Remarkably, the air conditioning system accounts for a significant part of energy consumption in TBS. In this work, passive radiative sky cooling technology has been studied to explore its application potential for TBS. We built a simulation model in DeST to investigate the effect of various envelope thermophysical properties on TBS energy saving. The main influencing factors of the radiative sky cooling on TBS energy saving have been concluded and guidance has been raised for further application. An optimized envelope design combining radiative sky cooling with appropriate heat transfer coefficients has been proposed. The energy-saving and economic analysis of the optimized envelope design at different areas shows that, except for the low heat density TBS in severe cold areas, the annual energy-saving rate is 6.77%–64.29%, and the annual total energy saving is 21.94 kWh/m2–52.74 kWh/m2. The payback period is 1.55–4.67 years, and the maximum acceptable cost limited to a 5-year payback period is $3.21/m2–$9.67/m2.

References

【1】
【1】
 
 
Building Simulation
Pages 1775-1787

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Cui Z, Guo C, Zhao D. Energy-saving and economic analysis of passive radiative sky cooling for telecommunication base station in China. Building Simulation, 2022, 15(10): 1775-1787. https://doi.org/10.1007/s12273-022-0894-z

1783

Views

27

Crossref

25

Web of Science

27

Scopus

5

CSCD

Received: 19 December 2021
Revised: 27 February 2022
Accepted: 28 February 2022
Published: 16 March 2022
© Tsinghua University Press 2022