Research Article

Evaluation of the performance of demand control ventilation system for school buildings located in the hot climate of Saudi Arabia

Alaa Alaidroos1( )Ayad Almaimani2Moncef Krarti3Ammar Dahlan2Rahif Maddah2
Architectural Engineering Department, King Abdulaziz University, Rabigh, Saudi Arabia
Faculty of Architecture and Planning, King Abdulaziz University, Jeddah, Saudi Arabia
Building Systems Program, University of Colorado Boulder, Boulder, CO, USA
Show Author Information

Abstract

The advantages of the demand control ventilation system (DCV) have been widely discussed in previous research studies. However, the literature has not addressed the benefits of DCV on controlling indoor CO2 concentration and minimizing cooling energy consumption for school buildings located in extremely hot climates. Therefore, this paper contributes to the development of DCV and mechanical ventilation systems through a comprehensive evaluation of these systems to maintain acceptable indoor air quality (IAQ) while minimizing cooling energy demands for school buildings located in the harsh hot climate of Saudi Arabia. The evaluation is based on a calibrated whole-building energy model and validated IAQ predictions using field data obtained from a school case study in Jeddah. The results of this research study confirm that hourly and sub-hourly monitoring of indoor CO2 concentration is required to ensure optimal design and operation of the ventilation systems in schools. In addition, the analyses indicate that a 13% increase in cooling energy end-use can result for any additional 0.1 students/m2 density increase in the classrooms. However, the energy penalties related to ventilation needs can be reduced by up to 25% using DCV instead of conventional mechanical ventilation systems for school buildings located in Saudi Arabia's hot climate.

References

【1】
【1】
 
 
Building Simulation
Pages 1067-1082

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Alaidroos A, Almaimani A, Krarti M, et al. Evaluation of the performance of demand control ventilation system for school buildings located in the hot climate of Saudi Arabia. Building Simulation, 2022, 15(6): 1067-1082. https://doi.org/10.1007/s12273-021-0854-z

1199

Views

17

Crossref

17

Web of Science

19

Scopus

0

CSCD

Received: 08 July 2021
Revised: 09 October 2021
Accepted: 15 October 2021
Published: 16 November 2021
© Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2021