Research Article

Investigation of the influence of groundwater seepage on the heat transfer characteristics of a ground source heat pump system with a 9-well group

Yu Wang( )Zhicheng LiuXiaolei YuanXiaofeng NiuJinxiang Liu
College of Urban Construction, Nanjing Tech University, No. 200 North Zhongshan Road, Nanjing 210009, China
Show Author Information

Abstract

The U-type ground heat exchanger is a significant component of the ground source heat pump (GSHP) system, transferring heat from the soil for the air conditioning requirements. Heat accumulation becomes a common problem for the practical application of such systems in southern China. Moreover, the buried pipes containing heat exchangers are constructed in a group form, making the heat accumulation situation more severe and complex. A 3-dimensional simulation model of a 9-well buried pipe group was established and validated by a thermal response test conducted in Nanjing, China. On the basis of this model, the influence of underground seepage water temperature and flow rate on thermal distribution was investigated. Subsequently, the heat transfer capacity of single-well depth in a heat exchanger under varying conditions was calculated. It is concluded that a serious heat accumulation occurs without groundwater seepage. With seepage flow, the heat accumulation can be dissipated. Lower seepage temperature has a modestly beneficial effect on the heat dissipation. The heat accumulation can be better dissipated and the heat transfer capacity per well depth can be improved with greater seepage flow rate.

References

【1】
【1】
 
 
Building Simulation
Pages 857-868

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Wang Y, Liu Z, Yuan X, et al. Investigation of the influence of groundwater seepage on the heat transfer characteristics of a ground source heat pump system with a 9-well group. Building Simulation, 2019, 12(5): 857-868. https://doi.org/10.1007/s12273-019-0526-4

958

Views

19

Crossref

N/A

Web of Science

22

Scopus

0

CSCD

Received: 30 August 2018
Revised: 21 December 2018
Accepted: 13 February 2019
Published: 26 April 2019
© Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2019