Assessing dynamic efficiency of air curtain in reducing whole building annual energy usage

Sherif GoubranDahai QiLiangzhu (Leon) Wang( )
Centre for Zero Energy Building Studies, Department of Building, Civil and Environmental Engineering, Concordia University, 1455 de Maisonneuve Blvd. West, Montreal, Quebec, H3G 1M8, Canada
Show Author Information

Abstract

The efficiency of air curtain in reducing infiltration and associated energy usage is currently evaluated statically by using an efficiency factor, ηair, based on single steady/static condition, which is often not the case for actual buildings under variable weather conditions and door usages. Based on a new method to consider these dynamic effects on air curtains, this study uses a dynamic efficiency factor ηB in terms of whole building site end-use energy to assess the efficiency of air curtains when compared to single doors (i.e. without air curtains) and vestibule doors. Annual energy simulations were conducted for two reference building models considering their specific door usage schedules in 16 climate zone locations in the North America. The variations of the proposed efficiency factor for different climate zones illustrated the dynamic impacts of weather, building, unit fan energy and door usage frequency on air curtain efficiency. A sensitivity study was also conducted for the operation temperature conditions of air curtain and showed that ηB also considers these operational conditions. It was thus concluded that using whole building site end-use energy to calculate the efficiency factor, ηB, can provide more realistic estimates of the performance of air curtains operations in buildings than the existing static efficiency factor.

References

【1】
【1】
 
 
Building Simulation
Pages 497-507

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Goubran S, Qi D, Wang L(. Assessing dynamic efficiency of air curtain in reducing whole building annual energy usage. Building Simulation, 2017, 10(4): 497-507. https://doi.org/10.1007/s12273-017-0349-0

1251

Views

26

Crossref

N/A

Web of Science

26

Scopus

3

CSCD

Received: 18 October 2016
Revised: 27 December 2016
Accepted: 03 January 2017
Published: 10 February 2017
© Tsinghua University Press and Springer-Verlag Berlin Heidelberg 2017