Analytical solution for heat transfer in a multilayer floor of a radiant floor system

Qing-qing Li1,2, Chao Chen1( ), Ye Zhang1, Jie Lin1, Hao-shu Ling1, Yun Ma1
The College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China
College of Architectural Engineering, Qingdao Agricultural University, Qingdao 266109, China
Show Author Information

Abstract

In radiant floor systems, the distribution of the floor surface temperature, which can be used to determine the mean temperature and the lowest/highest temperature of the floor surface, is an important parameter. The mean temperature of the floor surface determines cooling/heating capacity and indoor thermal comfort. The lowest surface temperature, which considers the dew point in an indoor environment, is a crucial factor in the prevention of condensation on a floor surface. The highest surface temperature is typically considered for local thermal comfort. In this paper, an analytical solution for heat transfer in a multilayer floor structure of a radiant floor system is proposed based on the analysis of the heat transfer process of a multilayer floor, equivalent thermal resistance and separation of variables method. The corresponding formulas are derived to estimate the distribution of floor surface temperature. The calculation results are validated by experiments. The calculation and experimental results show good accordance. The absolute error between the calculation and experimental results for floor surface temperature is within 0.3ºC. A method for the calculation of the dimensionless temperature of the floor surface, which can be used for radiant heating and cooling systems, is provided. Using this proposed method, the distribution of floor surface temperature and the influence of floor structure parameters on the thermal performance of floors can be estimated and analyzed.

References

【1】
【1】
 
 
Building Simulation
Pages 207-216

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Li Q-q, Chen C, Zhang Y, et al. Analytical solution for heat transfer in a multilayer floor of a radiant floor system. Building Simulation, 2014, 7(3): 207-216. https://doi.org/10.1007/s12273-013-0152-5

1013

Views

34

Crossref

N/A

Web of Science

35

Scopus

0

CSCD

Received: 31 May 2013
Revised: 17 July 2013
Accepted: 25 July 2013
Published: 12 November 2013