Investigating a safe ventilation rate for the prevention of indoor SARS transmission: An attempt based on a simulation approach

Yi Jiang( )Bin ZhaoXiaofeng LiXudong YangZhiqin ZhangYufeng Zhang
Department of Building Science, School of Architecture, Tsinghua University, Beijing 100084, China
Show Author Information
An erratum to this article is available online at:

Abstract

This paper identifies the "safe ventilation rate" for eliminating airborne viral infection and preventing cross-infection of severe acute respiratory syndrome (SARS) in a hospital-based setting. We used simulation approaches to reproduce three actual cases where groups of hospital occupants reported to be either infected or not infected when SARS patients were hospitalized in nearby rooms. Simulations using both computational fluid dynamics (CFD) and multi-zone models were carried out to understand the dilution level of SARS virus-laden aerosols during these scenarios. We also conducted a series of measurements to validate the simulations. The ventilation rates (dilution level) for infection and non-infection were determined based on these scenarios. The safe ventilation rate for eliminating airborne viral infection is to dilute the air emitted from a SARS patient by 10000 times with clean air. Dilution at lower volumes, specifically 1000 times, is insufficient for protecting non-infected people from SARS exposure and the risk of infection is very high. This study provides a methodology for investigating the necessary ventilation rate from an engineering viewpoint.

References

【1】
【1】
 
 
Building Simulation
Pages 281-289

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Jiang Y, Zhao B, Li X, et al. Investigating a safe ventilation rate for the prevention of indoor SARS transmission: An attempt based on a simulation approach. Building Simulation, 2009, 2(4): 281-289. https://doi.org/10.1007/s12273-009-9325-7

1042

Views

62

Downloads

62

Crossref

N/A

Web of Science

70

Scopus

0

CSCD

Received: 14 August 2009
Revised: 01 November 2009
Accepted: 02 November 2009
Published: 04 December 2009