Case Study on the Thermal Management and Energy Efficiency of Under-floor Air Distribution Data Centers Using Blind Plates

Qiming Gao1Yu Zhang2Xiumin Feng2Zhongbin Zhang2( )
Hefei General Machinery Research Institute Co., Ltd., Hefei, 230031, China
School of Energy and Mechanical Engineering, Nanjing Normal University, Nanjing, 210023, China
Show Author Information

Abstract

Data center computer room air-conditioning equipment operates for prolonged periods, and its performance must be tested and evaluated annually to ensure safe and efficient operation. This study conducts field measurements on the server layout, blind plate structure, and working condition adaptability in the rack. The thermal environment of a data center using the closed cold aisle underfloor air distribution system is studied, and the thermal environment safety and energy efficiency throughout the year are evaluated through thermal performance indicators and energy efficiency indicators. The results show that it is recommended to install a rack with a power of more than 2 kW in the middle area of the cold aisle. Installing a blind plate in the gap between the racks can promote the circulation of cold air inside the server, reduce the backflow interference of hot air, and reduce the maximum outlet temperature by 3.32 ℃. The average supply air speed was reduced by approximately 24%. Under summer operating conditions, the PUE, WUE, and CUE of the data center were approximately 1.2, 3.5, and 0.84, respectively, and the WUE exhibited strong seasonality. Under winter operating conditions, free cooling can effectively reduce the energy consumption of data centers. In addition, the overheating problem of the racks at the end of the cold aisle of the data center is significant. The cabinet cooling index of the 16 racks was less than 90%, and the heat loss was high.

CLC number: TB61+1;TB69 Document code: A Article ID: 0253-4339(2024)03-0129-14

References

【1】
【1】
 
 
Journal of Refrigeration
Pages 129-142

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Gao Q, Zhang Y, Feng X, et al. Case Study on the Thermal Management and Energy Efficiency of Under-floor Air Distribution Data Centers Using Blind Plates. Journal of Refrigeration, 2024, 45(3): 129-142. https://doi.org/10.3969/j.issn.0253-4339.2024.03.129

1

Views

0

Downloads

0

Crossref

0

CSCD

Received: 04 May 2023
Revised: 27 June 2023
Accepted: 09 August 2023
Published: 16 June 2024
© 2024 The Editorial Office of Journal of Refrigeration

This is an open access article under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0, http://creativecommons.org/licenses/by/4.0/).