AI Chat Paper
Note: Please note that the following content is generated by AMiner AI. SciOpen does not take any responsibility related to this content.
{{lang === 'zh_CN' ? '文章概述' : 'Summary'}}
{{lang === 'en_US' ? '中' : 'Eng'}}
Chat more with AI
PDF (11.5 MB)
Collect
Submit Manuscript AI Chat Paper
Show Outline
Outline
Show full outline
Hide outline
Outline
Show full outline
Hide outline
Publishing Language: Chinese | Open Access

Influence of R32 Leak Detection Position on Indoor Safety

Wenqiang ZhangGuanming Guo( )Xiaohui GuoJianjun MengHeng Zhang
Qingdao Hisense Hitachi Air-conditioning System Co., Ltd., Qingdao, 266555, China
Show Author Information

Abstract

In this study, the leakage diffusion and concentration distribution characteristics of R32 refrigerants from a wall-mounted split air-conditioner indoor unit are analyzed by combining experiments and simulations under different leak locations, refrigerant leak rates, and operating conditions. Safety is compared and evaluated based on whether the R32 mass fraction reaches the R32 refrigerant detector alarm concentration (4% LFL), the positions of the responsive detectors, and the lower flammability limit (LFL) area. The results show that the response time of the detectors inside the indoor unit is approximately 40 s and 50% faster than that located in the room. The experimental and numerical results show a high consistency. The diffusion law of R32 is different at different leak locations. The leak rate of R32 slightly influences the concentration distribution in the indoor unit. The area where the 4% LFL is reached when the air conditioning is ventilated is four times smaller than when the air conditioning is turned off. The best position to install the R32 refrigerant detector is the lower area between the electrical box and the front heat exchanger. When R32 leaks at the fin of the heat exchanger, the R32 refrigerant detector fails to respond, and the refrigerant continues to leak into the room, posing a safety hazard. The LFL volume is approximately 3×10-6 m3. The LFL region is a small area around the R32 leak port, and its safety risk is low.

CLC number: TB61+1;TB657.2 Document code: A Article ID: 0253-4339(2024)03-0120-09

References

【1】
【1】
 
 
Journal of Refrigeration
Pages 120-128

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Zhang W, Guo G, Guo X, et al. Influence of R32 Leak Detection Position on Indoor Safety. Journal of Refrigeration, 2024, 45(3): 120-128. https://doi.org/10.3969/j.issn.0253-4339.2024.03.120

1

Views

0

Downloads

0

Crossref

0

CSCD

Received: 07 April 2023
Revised: 09 June 2023
Accepted: 31 July 2023
Published: 16 June 2024
© 2024 The Editorial Office of Journal of Refrigeration

This is an open access article under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0, http://creativecommons.org/licenses/by/4.0/).