Investigating Optimal Operation of Buried Pipe Side Water System of Ground Source Heat Pump

Pengxu Chen1Bo Xu1Zhenqian Chen1( )Xiangyan Chen2
School of Energy and Environment, Southeast University, Nanjing, 210096, China
Jiangsu Shengshi Electromechanical Engineering Co., Ltd., Lianyungang, 222000, China
Show Author Information

Abstract

Based on the measured data from a typical ground-source heat pump air conditioning project in Wuxi, Jiangsu Province, with the primary objective of minimizing total energy consumption on the ground-source side, an equipment model for optimizing the operating conditions of the ground-source heat pump is constructed in this study. The optimal control strategy is compared with two traditional control strategies, and recommendations for further optimization are presented. The results showed that the optimal control strategy based on the load had a significantly better energy-saving effect than that of the constant-frequency control strategy. On typical test days in winter and summer, it achieved average energy savings of 28.43% and 21.21%, respectively, resulting in energy savings of 3.61% and 2.21%, respectively, when compared to the 5 ℃ temperature difference frequency conversion strategy. Moreover, it was found that the traditional constant temperature difference control strategy should elevate the temperature difference by 1-5 ℃ from the 5 ℃ baseline, to enhance energy savings when the load ratio exceeded 60%. These findings offer valuable guidance for optimizing the variable-flow strategy of ground-source side water systems in ground-source heat pumps.

CLC number: TB657.5;TK523 Document code: A Article ID: 0253-4339(2024)01-0110-08

References

【1】
【1】
 
 
Journal of Refrigeration
Pages 110-117

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Chen P, Xu B, Chen Z, et al. Investigating Optimal Operation of Buried Pipe Side Water System of Ground Source Heat Pump. Journal of Refrigeration, 2024, 45(1): 110-117. https://doi.org/10.3969/j.issn.0253-4339.2024.01.110

6

Views

0

Downloads

0

Crossref

0

CSCD

Received: 13 December 2022
Revised: 18 February 2023
Accepted: 14 March 2023
Published: 16 February 2024
© 2024 The Editorial Office of Journal of Refrigeration

This is an open access article under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0, http://creativecommons.org/licenses/by/4.0/).