Discover the SciOpen Platform and Achieve Your Research Goals with Ease.
Search articles, authors, keywords, DOl and etc.
This paper presents an adaptive staged overcurrent protection system based on predicted post-fault Thevenin equivalent parameters. The presented protection scheme can be used in a distribution system with more than one Inverter Interfaced Distribution Generators (IIDGs). To implement the protection system, equations of pre-fault and post-fault Thevenin equivalent parameters are obtained and relationship between them is revealed. Then protection’s stage Ⅰ and stage Ⅱ trip currents are calculated by an easy algorithm based on that relationship. What’s more, a sensitivity verification is applied to the Stage Ⅱ operating current, enabling both Stage Ⅰ and Stage Ⅱ to protect the entire line, similar to conventional overcurrent (OC) protection. To verify equations and ensure protection system working normally, a distribution system is built in PSCAD/EMTDC. Simulation and calculation results show that the sensitivity and the selectivity of the protection system satisfy the need of an OC protection.
This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
Comments on this article