Discover the SciOpen Platform and Achieve Your Research Goals with Ease.
Search articles, authors, keywords, DOI, etc.
Preventive maintenance (PM) enhances the reliability of an ultra-high-voltage DC (UHVDC) line. However, it introduces new states and complicates the task of determining the reliability parameters of the component with PM. The hierarchical connection (HC) of the inverter improves the flexibility of UHVDC, but the state spaces of the inverter and UHVDC-HC are determined by capacity distribution between the high terminal (HT) and low terminal (LT), which has not been studied yet. In this paper, the reliability of UHVDC-HC with the PM is studied. First, with the impact of PM described by a nonlinear coefficient, the state space of the components with PM is aggregated. It is the same size as without PM. The only difference is the transition rate. Second, considering power distribution between the HT/LT and its dependence on the state of the rectifier, new capacity levels of HT/LT, e.g., 75%/2, 50%/3, are defined. Third, with capacity levels of the HT/LT differentiated, 2 existing reliability indices are extended, and 2 are newly defined. Finally, a sensitivity model of the reliability of the UHVDC-HC to its parameters and the PM period is proposed.
This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
Comments on this article