Regular Paper | Open Access

Impedance-phase and Magnitude Control Method to Improve Stability of Grid-connected Inverters in Weak Grid

Chunming Tu1, Jiayuan Gao1( ), Fan Xiao1, Qi Guo1, Fei Jiang2
College of Electrical and Information Engineering, Hunan University, Changsha 410082, China
School of Electrical and Information Engineering, Changsha University of Science and Technology, Changsha 410004, China
Show Author Information

Abstract

Grid impedance and phase-locked loop (PLL) are critical factors for the stability of the grid-connected inverters (GCIs) in a weak grid. They are the positive feedback control loops formed by PLL in the GCI with grid impedance. It is prone to GCI instability, especially in the case of the higher PLL bandwidth. A novel impedance-phase and magnitude control strategy is proposed to improve stability of GCI with different grid impedance. Moreover, a detailed design of control loop and parameter calculation for the impedance-phase and magnitude control strategy are introduced. First, PLL output impedance is reshaped to broaden the frequency range of the GCI phase-frequency characteristic curve above the −90° line towards the low-frequency band. In addition, current loop output impedance is reshaped to maintain the phase margin (PM) of the GCI near to 45°. Meanwhile, the magnitude of GCI output impedance is also increased significantly. Stability of the GCI in a weak grid is enhanced by adopting the proposed control strategy. Simulation and experimental results verify the analysis and the proposed method.

References

【1】
【1】
 
 
CSEE Journal of Power and Energy Systems
Pages 1755-1769

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Tu C, Gao J, Xiao F, et al. Impedance-phase and Magnitude Control Method to Improve Stability of Grid-connected Inverters in Weak Grid. CSEE Journal of Power and Energy Systems, 2025, 11(4): 1755-1769. https://doi.org/10.17775/CSEEJPES.2021.03560

731

Views

59

Downloads

1

Crossref

4

Web of Science

5

Scopus

1

CSCD

Received: 08 May 2021
Revised: 15 July 2021
Accepted: 13 December 2021
Published: 05 September 2022
© 2021 CSEE.

This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).