Dynamics of glowing contacts triggered by poor electrical contact

Jing ZHANG1, Tao CHEN1( ), Lida HUANG1, Guofeng SU1,2, Zhanhui SUN1, Jianguo CHEN1
Institute of Public Safety Research, Department of Engineering Physics, Tsinghua University, Beijing 100084, China
Hefei Institute for Public Safety Research, Tsinghua University, Hefei 230601, China
Show Author Information

Abstract

Glowing contacts triggered by poor electrical contact are one of the most important ignition sources for fires. The glowing contacts with high temperature are commonly hidden in electric wires. The glowing contact involves complex coupling between the copper oxidation, heat transfer, and electric field. The relationships between the key parameters are investigated experimentally by measuring the growth rate of the oxide bridge length as well as the glowing contact resistance and temperature. The results show that the oxide bridge length and the glowing contact resistance increase with time. The maximum contact temperature increases with time up to 1 400-1 600℃. Increasing currents increase the oxide bridge growth rate and growth time. The increasing rate of the resistance first increases and then decreases with the current increase. The results further show that the glowing contact is due to interactions between the oxidation extent, the changes in the copper oxide resistivity with the current, and the increases in the specific heat with temperature.

CLC number: X915.5 Document code: A Article ID: 1000-0054(2022)06-1000-10

References

【1】
【1】
 
 
Journal of Tsinghua University (Science and Technology)
Pages 1000-1009

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
ZHANG J, CHEN T, HUANG L, et al. Dynamics of glowing contacts triggered by poor electrical contact. Journal of Tsinghua University (Science and Technology), 2022, 62(6): 1000-1009. https://doi.org/10.16511/j.cnki.qhdxxb.2022.22.034

1534

Views

25

Downloads

0

Crossref

4

Scopus

2

CSCD

Received: 16 February 2022
Published: 15 June 2022
© Journal of Tsinghua University (Science and Technology). All rights reserved.