Discover the SciOpen Platform and Achieve Your Research Goals with Ease.
Search articles, authors, keywords, DOl and etc.
R1270 and R290 are alternative refrigerants with great potential. In this study, the influence of the refrigerant charge on the performance of the heat-pump water heater with R1270 and R290, the temperature distribution of the heat transfer fluids in the condenser, and the feasibility of replacing R22 with natural refrigerants were investigated. The results indicate that the refrigerant charge has a considerable influence on the cycle performance and the temperature distribution of the heat-transfer fluids in both systems. At the same optimal charge (0.90 kg), the R1270 and R290 systems achieved a maximum coefficient of performance (COP) of 4.443 and 4.317, respectively. At different refrigerant charges, two heat transfer pinch points and two maximum heat transfer temperature differences occurred in the condensers of both systems, and the locations of the first pinch point and the second maximum temperature difference point showed similar migrations with changes in refrigerant charge. Compared with the R22 system, both the R1270 and R290 systems, at optimal charge, achieved significantly better COP and discharge temperatures, exhibited relatively equivalent discharge pressures, and their heating capacities increased by 7.05% and decreased by 10.65%, respectively. Hence, R1270 can be preferred over R290 for replacing R22 in a heat-pump water heater.
This is an open access article under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0, http://creativecommons.org/licenses/by/4.0/).
Comments on this article