Cooling System for Data Centers Based on the Air-Water-Air Principle with Increased Temperature Differential

Yang JingXiaoyun Xie( )Yi Jiang
Building Energy Research Center, Tsinghua University, Beijing, 100084, China
Show Author Information

Abstract

Improving the energy efficiency of data centers by conserving energy in cooling systems is a priority strategy. In this study, thermal analysis of the prevailing air-water-air cooling system revealed inefficiencies caused by a significant discrepancy in the flow rate between the air and water sides of the server room air conditioning system. To mitigate such discrepancy, a new system architecture with a high-temperature differential on the waterside was proposed. Compared with a conventional system with a small temperature differential, the proposed high-temperature differential cooling system substantially augmented the proportion of natural cooling throughout the year, reduced the energy consumption of pumping fluids, and reduced the total energy consumption of the cooling system by approximately 20%-30%. Although the introduction of a high-temperature differential cooling system requires an increase in the heat exchange area and an increase in the cost of air conditioning for the server room, it concurrently reduces the investment in cooling towers, chillers, circulating pumps, chilled water storage tanks, pipelines, and valves, ultimately reducing the total investment in the cooling system by 15%-25%. Furthermore, the high-temperature differential cooling system facilitates operational adjustments, decouples control from external temperature variations and IT load changes, and minimizes maintenance requirements.

CLC number: TB61+1; TP308 Document code: A Article ID: 0253-4339(2025)03-0113-10

References

【1】
【1】
 
 
Journal of Refrigeration
Pages 113-122

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Jing Y, Xie X, Jiang Y. Cooling System for Data Centers Based on the Air-Water-Air Principle with Increased Temperature Differential. Journal of Refrigeration, 2025, 46(3): 113-122. https://doi.org/10.12465/j.issn.0253-4339.2025.03.113

65

Views

0

Downloads

0

Crossref

1

CSCD

Received: 19 September 2024
Revised: 10 December 2024
Accepted: 11 December 2024
Published: 16 June 2025
© 2025 The Editorial Office of Journal of Refrigeration

This is an open access article under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0, http://creativecommons.org/licenses/by/4.0/).