Model for Carried Out Liquid Fraction from Accumulator of Compressor Used in Room Air-Conditioners

Jiansheng Liao1,2Ziteng Yan1Feilong Zhan1Guoliang Ding1( )Liyu Zheng2
Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai, 200240, China
GD Meizhi Compressor Co., Ltd., Foshan, 528300, China
Show Author Information

Abstract

To prevent issues such as liquid hammer or oil starvation resulting from excessive or insufficient liquid carried from the accumulator in air conditioner compressors, controlling the liquid mass within reasonable limits is essential. This requires an accurate prediction method for evaluating the liquid carryover. The purpose of this study is to develop a model to predict the mass of liquid carried from an accumulator and to validate this model experimentally. The flow process of the refrigerant-oil mixture is divided into four subprocesses: vapor-liquid phase change, vapor-liquid interphase mass transfer, inlet tube injection flow, and outlet tube convergence flow. Four submodels are established to describe these subprocesses, and an algorithm based on the backward difference method is developed to solve them. An experimental apparatus is set up to measure the liquid carryover from the accumulator. The experimental results show that the deviation between the model predictions and experimental values is within ±3%, with an average deviation of 0.7%. The proposed accumulator model can be used to design the structural parameters of the oil return hole, avoiding liquid hammer and oil starvation in compressors.

CLC number: TB61+1; TB652; TB657.2 Document code: A Article ID: 0253-4339(2026)02-0123-09

References

【1】
【1】
 
 
Journal of Refrigeration
Pages 123-131

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Liao J, Yan Z, Zhan F, et al. Model for Carried Out Liquid Fraction from Accumulator of Compressor Used in Room Air-Conditioners. Journal of Refrigeration, 2026, 47(2): 123-131. https://doi.org/10.12465/issn.0253-4339.20241021001

456

Views

5

Downloads

0

Crossref

0

CSCD

Received: 21 October 2024
Revised: 18 November 2024
Accepted: 09 December 2024
Published: 16 April 2026
© 2026 The Editorial Office of Journal of Refrigeration

This is an open access article under the terms of the Creative Commons Attribution 4.0 International License (CC BY 4.0, http://creativecommons.org/licenses/by/4.0/).