Publishing Language: Chinese | Open Access

Online calculation method for frequency disturbance propagation combining approximate analytical solution and physics-informed

Yong QIAO1Zhong CHEN1Yunsong YAN1,2Xiong CHEN2Yaran LI3Xinyao ZHU3
School of Electrical Engineering, Southeast University, Nanjing 210096, China
NARI Technology Co., Ltd., Nanjing 211106, China
State Grid Jiangsu Electric Power Co., Ltd. Research Institute, Nanjing 211103, China
Show Author Information

Abstract

Frequency disturbances caused by power system faults propagate in the form of electromechanical waves. This propagation process affects the frequency response analysis and decision-making of safety control measures such as frequency stability maintenance and under-frequency load shedding. The conventionally used offline simulation method offers high calculation accuracy, but it has limitations such as poor adaptability to complex and variable new power systems and insufficient online computing capability. An online calculation method is proposed for frequency propagation based on approximate analytical solutions and physics-informed neural network (PINN). Firstly, a partial differential equation model for the propagation of electromechanical disturbance frequencies is established. Through engineering simplifications, an analytical expression of frequency disturbance with respect to time and position is derived, which meets the requirement for fast calculation of frequency disturbances but suffers from reduced calculation accuracy due to the simplifications. Subsequently, PINN is introduced to improve calculation accuracy. A small amount of high-precision simulation data and a large amount of low-precision data quickly obtained from analytical solutions are used as samples, which solves the problem of excessive sample generation time. Furthermore, the electromechanical disturbance frequency propagation model before simplification is incorporated into the network layer as a physical constraint. This not only ensures fast calculation but also enhances the calculation accuracy and generalization performance across different operating scenarios. Finally, a case study system is built using RT-Lab and PyTorch. The feasibility and superiority of the proposed method are verified through simulation and comparative analysis.

CLC number: TM712 Document code: A

References

【1】
【1】
 
 
Electric Power Engineering Technology
Pages 1-11

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
QIAO Y, CHEN Z, YAN Y, et al. Online calculation method for frequency disturbance propagation combining approximate analytical solution and physics-informed. Electric Power Engineering Technology, 2026, 45(6): 1-11. https://doi.org/10.12158/j.2096-3203.2026.06.001

5

Views

0

Downloads

0

Crossref

0

Scopus

Received: 12 October 2025
Revised: 28 December 2025
Published: 30 June 2026
© After publication of the article, the authors shall own the right of signature. 2026.

The authors can use or share the published article under the Attribution-Non Commercial 4.0 International (CC BY-NC 4.0) license.