Application of Six-Sequence Fault Components in Fault Location for Joint Parallel Transmission Line

Chunju FAN( )Huarong CAIWeiyong YU
Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200030, China
Show Author Information

Abstract

A new fault location method based on six-sequence fault components was developed for parallel lines based on the fault analysis of a joint parallel transmission line. In the six-sequence fault network, the ratio of the root-mean square value of the fault current from two terminals is the function of the line impedance, the system impedance, and the fault distance away from the buses. A fault location equation is given to relate these factors. For extremely long transmission lines, the distributed capacitance is divided by the fault point and allocated to the two terminals of the transmission line in a lumped parameter to eliminate the influence of the distributed capacitance on the location accuracy. There is no limit on fault type and synchronization of the sampling data. Simulation results show that the location accuracy is high with an average error about 2%, and it is not influenced by factors such as the load current, the operating mode of the power system, or the fault resistance.

References

【1】
【1】
 
 
Tsinghua Science and Technology
Pages 247-253

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
FAN C, CAI H, YU W. Application of Six-Sequence Fault Components in Fault Location for Joint Parallel Transmission Line. Tsinghua Science and Technology, 2005, 10(2): 247-253. https://doi.org/10.1016/S1007-0214(05)70062-6

1

Views

0

Downloads

0

Crossref

N/A

Web of Science

0

Scopus

0

CSCD

Received: 15 March 2003
Published: 01 April 2005
© Tsinghua University Press 2005