Discover the SciOpen Platform and Achieve Your Research Goals with Ease.
Search articles, authors, keywords, DOI, etc.
The photoacoustic spectroscopy apparatus based on an external cavity quantum cascade laser was employed to simultaneously detect four SF6 decomposition by-products, i.e., SO2F2, SOF2, CF4, and SO2 for the application in diagnostics of the SF6 insulation equipment widely used in high-voltage transmission lines. The influence of background gases SF6 and N2 with the He addition in different ratios on the SOF2 photoacoustic signal was investigated, with the pure SF6 showing the most pronounced enhancement effect on the photoacoustic signal of the target analyte. The limit of detection of SOF2 in pure SF6 was estimated by comparing the limits of detection of SOF2, CF4, and SO2 in the 95% SF6/5% He combination and pure SF6. The estimated detection limits for SO2F2, SOF2, CF4, and SO2 were 635.4 ppb, 24.0 ppb, 10.3 ppb, and 97.8 ppb, respectively. Finally, the concentration of each decomposition component in the gas mixture of SO2F2, SOF2, CF4, and SO2 in the 95% SF6/5% He background gas was quantified by multiple linear regression.
This article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.
Comments on this article