@article{Zhu2026, 
author = {Renlong Zhu and Xiaoping Zhou and Hanhang Yin and Yandong Chen and An Luo and Lerong Hong and Lingfeng Deng and Hanting Peng},
title = {Commutation Failure Fault Level Calculation Method Under Three-phase-to-ground Faults Considering Multi-factor Influence},
year = {2026},
journal = {CSEE Journal of Power and Energy Systems},
volume = {12},
number = {5},
pages = {2480-2488},
keywords = {Commutation failure (CF), commutation failure fault level (CFFL) calculation, commutation failure mitigation capability evaluation, line-commutated-converter-based high-voltage direct-current (LCC-HVDC)},
url = {https://www.sciopen.com/article/10.17775/CSEEJPES.2022.06630},
doi = {10.17775/CSEEJPES.2022.06630},
abstract = {Earlier works have reported some critical commutating voltage or commutation failure immunity index calculation methods for commutation failure (CF) mitigation capability evaluation of line-commutated-converter-based high-voltage direct-current. However, accuracy of earlier methods is limited since they only consider commutating voltage drop and DC current rise. Hence, a commutation failure fault level calculation method under three-phase-to-ground faults considering multi-factor influence is proposed in this paper. First, transient time-domain response of DC current after fault is gained and DC current harmonics are calculated by Fast Fourier Transform. Then, AC current harmonics are estimated based on the coupling relationship of DC current and AC current of the inverter. Furthermore, supply voltage-time area and zero-crossing considering the harmonic voltage are estimated. Then, dynamic interaction between AC and DC system caused by constant extinction angle controller is considered by the power flow equation. Finally, discrete commutation processes are constructed based on commutation voltage-time area rule to determine occurrence of CF under different fault levels. Calculation results of the tradition method and the proposed method are compared with simulation results based on PSCAD/EMTDC.}
}