@article{Wu2024, 
author = {Jing Wu and Libo Yan and Lin Ye and Minxia Li and Yitai Ma and Pai Wang},
title = {Influence Factors of Ice Surface Temperature in Direct Evaporation CO2 Artificial Ice},
year = {2024},
journal = {Journal of Refrigeration},
volume = {45},
number = {4},
pages = {114-123},
keywords = {CO2, direct evaporation, artificial ice rink, ice surface temperature},
url = {https://www.sciopen.com/article/10.3969/j.issn.0253-4339.2024.04.114},
doi = {10.3969/j.issn.0253-4339.2024.04.114},
abstract = {In this study, using a direct evaporation indoor CO2 artificial ice rink as the research object, we establish a mathematical model for the stable temperature field of the indoor ice rink to analyze the influence of mass flux, tube spacing, oil content, and other factors on ice surface temperature and ice temperature difference when the evaporating temperature is -13 ℃ in a 12.7 mm diameter copper pipe. Results show that an increase in the lubricating oil content increases the pressure drop in the pipe and the temperature difference between the inlet and outlet of the ice surface. However, because the pipe diameter and mass flux investigated in this study are relatively large, the influence range is small. The temperature distribution on the ice surface is mainly affected by the distance between the cooling pipes and the mass flux. The temperature difference of the ice surface increases with an increase in tube spacing and mass flux. To ensure a temperature difference of the ice surface less than 0.5 ℃, the recommended mass flux should be less than 200 kg/(m2·s), and the tube spacing should be less than 90 mm.}
}