@article{Qiu2025, 
author = {Senyue Qiu and Lei Qi and Xiangyu Zhang and Wuyu Zhang and Xiang Cui and Ningming Guo},
title = {Parameter Design and Transfer Characteristic Optimization of Floating-ground Capacitive Voltage Divider for Wideband High Voltage Measurement},
year = {2025},
journal = {CSEE Journal of Power and Energy Systems},
volume = {11},
number = {4},
pages = {1693-1703},
keywords = {Capacitive voltage divider floating ground measurement wideband characteristic},
url = {https://www.sciopen.com/article/10.17775/CSEEJPES.2021.06830},
doi = {10.17775/CSEEJPES.2021.06830},
abstract = {Voltage measuring equipment in power grids often requires capacitive voltage dividers to realize conversion of high voltage electrical quantities to low voltage signal quantities. The new floating-ground capacitive voltage divider (FG-CVD) can eliminate original lumped capacitors and its supporting insulation structures by adopting precisely designed parasitic capacitance as a high voltage arm capacitor, which can greatly save cost and volume. However, the utilization of parasitic capacitance not only makes FG-CVD sensitive to external conductor interference, but also causes transient waveform distortion, especially when the connecting lead between the FG-CVD and high-voltage conductor is lengthy. On the basis of transfer characteristic analysis, this paper proposes a complete parameter design method for FG-CVD to improve stability of its transfer ratio under interference of the external conductor. Moreover, by establishing a wideband equivalent model with lead inductance, the transient waveform distortion problem of FG-CVD is well explained, and a resistance compensation scheme is also proposed to reduce ratio error. Finally, a 500:1 FG-CVD prototype with a measurement bandwidth of 2MHz is developed. Experimental results show the prototype has high accuracy in both power frequency and lightning pulse voltage measurement, and ratio error decreases from 20.33% to less than 1.3%.}
}