With the sustained increase in the penetration rate of grid-forming (GFM) converters in power systems, problems such as overcurrent and transient instability during system faults have drawn significant attention. This paper proposes an enhanced dynamic dq-axis current-limiting strategy (ED-CLiS) for GFM converters, which improves transient stability across all stages before and after current limiting. First, a dynamic dq-axis current-limiting strategy (D-CLiS) is proposed. This strategy regulates the power angle to prevent it from going out of control during current limiting, which is achieved by controlling the d- and q-axis current reference values to reshape the