Regular Paper | Open Access

Real-time Harmonic Pollution Evaluation Considering Multiple Dynamic Customers

Shaohua Yang , Keng-Weng Lao( ), Hongxun Hui, Yulin Chen, Ningyi Dai
State Key Laboratory of Internet of Things for Smart City and Department of Electrical and Computer Engineering, University of Macau, Macao 999078, China
Show Author Information

Abstract

The widespread deployment of renewable energies and non-linear loads has led to serious harmonic pollution in electrical distribution networks. Evaluation of the harmonic contribution (HC) of each customer is a significant task for power quality management. Most previous studies focus on periodic evaluation methods, where numerous data have to be collected in advance over a period (e.g., one day). However, customer behaviors are time-varying and would lead to dynamic HCs, which can not be captured by traditional periodic evaluation methods. To address this issue, this paper presents a novel real-time HC evaluation method considering multiple dynamic customers. First, a two-stage iteration estimator is proposed based on the information fusion technique to quantify real-time HC of each customer. Then, to mitigate the negative effect of unknown background harmonics, a dominant index method is developed to determine credibility of the measurement data. On this basis, an adaptive gain selection strategy is proposed to improve accuracy of real-time HC evaluation. By doing so, the major harmonic contributor can be identified for implementing harmonic suppression and improving power quality. Finally, a typical IEEE system is utilized to verify the proposed methods. The results show that using the proposed method, evaluation errors can be reduced from about 10% to 2.5%. Moreover, the total harmonic distortion of voltage can be suppressed from 5.564% to 0.702%. Therefore, this research provides practical insights for addressing harmonic problems in power systems.

References

【1】
【1】
 
 
CSEE Journal of Power and Energy Systems
Pages 1093-1106

{{item.num}}

Comments on this article

Go to comment

< Back to all reports

Review Status: {{reviewData.commendedNum}} Commended , {{reviewData.revisionRequiredNum}} Revision Required , {{reviewData.notCommendedNum}} Not Commended Under Peer Review

Review Comment

Close
Close
Cite this article:
Yang S, Lao K-W, Hui H, et al. Real-time Harmonic Pollution Evaluation Considering Multiple Dynamic Customers. CSEE Journal of Power and Energy Systems, 2025, 11(3): 1093-1106. https://doi.org/10.17775/CSEEJPES.2022.06570

781

Views

62

Downloads

5

Crossref

23

Web of Science

24

Scopus

0

CSCD

Received: 28 September 2022
Revised: 28 December 2022
Accepted: 19 January 2023
Published: 20 April 2023
© 2022 CSEE.

This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).