Development and Tests of ZW-126/D2000-40 Vacuum Circuit Breakers with Controlled Switching Technology

Yu TianJiayuan XuYuan DengYongxing WangEnyuan Dong( )Jiyan Zou
Dalian University of Technology, Dalian 116024, China
State Grid Pinggao Group, Pingdingshan 467001, China
Show Author Information

Abstract

A ZW-126/D2000-40 type single-break vacuum circuit breaker (VCB) with controlled switching technology is designed and produced in this paper. The results of type tests based on IEC and GB standards are presented. A 126 kV single-break vacuum interrupter (VI) with 3/4 coil axial magnetic field (AMF) contacts is used in the VCB, which can interrupt short currents of 40 kA. The external insulation of the VI is provided by SF 6 at 0.1 MPa. In order to match the 126 kV single-break VI and controlled switching device, a long-stroke electro-magnetic force actuator (EMFA) with 16 kN closing holding force and 3.5 m/s average opening speed is designed. Moreover, a position tracking controlled switching device based on closed-loop control using the technology of a fuzzy control algorithm and pulse width modulation is applied to the controlled switching device. This device is applied to control the coil current of EMFA and the electromagnetic force, so as to control the EMFA to follow the ideal position curve. The type tests of 126 kV VCB are all passed according to the IEC62271-100 and GB1984-2014, including dielectric tests, basic short-circuit tests, short-line fault tests, out-of-phase tests, etc. The strong capacitive current breaking capacity and mechanical strength of the VCB are proved by the capacitive current switching test of class C2, electrical endurance test of class E2 and mechanical endurance test of class M2. The electromagnetic compatibility (EMC) tests are passed according to the IEC61000-4. The controlled switching test of capacitive current was successful according to IEC62271-302 and GB/T30846-2014, and the controlled switching accuracy is less than ± 0.5 ms. The test results show that the VCB has excellent performance, which has broad application prospects in special occasions at a 126 kV voltage level, such as a switching capacitor and no-load transformer, etc.

References

[1]
Z. Guo, X. W. Li, H. B. Su, Y. Zhang, Y. H. Wu, S. L. Jia, Y. Wang, and L. Gu, “Interrupting characteristics of paralleled SF6 circuit breakers with a highly coupled split reactor,”IEEE Transactions on Components, Packaging and Manufacturing Technology, vol. 7, no. 5, pp. 768776, May 2017.
[2]
B. Xu, R. Q. Ding, J. H. Zhang, L. F. Sha, and M. Cheng, “Multiphysics-coupled modeling: simulation of the hydraulic-operating mechanism for a SF6 high-voltage circuit breaker,”IEEE/ASME Transactions on Mechatronics, vol. 21, no. 1, pp. 379393, Feb. 2016.
[3]
W. J. Wen, Y. L. Huang, M. Al-Dweikat, Z. A. Zhang, T. H. Cheng, S. T. Gao, and W. D. Liu, “Research on operating mechanism for ultra-Fast 40.5-kV vacuum switches,”IEEE Transactions on Power Delivery, vol. 30, no. 6, pp. 25532560, Dec. 2015.
[4]
D. C. Huang, S. W. Shu, and J. J. Ruan, “Transient recovery voltage distribution ratio and voltage sharing measure of double- and triple-break vacuum circuit breakers,”IEEE Transactions on Components, Packaging and Manufacturing Technology, vol. 6, no. 4, pp. 545552, Apr. 2016.
[5]
X. F. Yao, J. W. Wang, Y. S. Geng, J. Yan, Z. Y. Liu, J. J. Yao, and P. Liu, “Development and type test of a single-break 126-kV/40-kA–2500-A vacuum circuit breaker,”IEEE Transactions on Power Delivery, vol. 31, no. 1, pp. 182190, Feb. 2016.
[6]
S. Kam, S. Nielsen, and G. Ledwich, “A systematic review of a statistical vacuum circuit breaker model for condition monitoring,”IEEE Transactions on Dielectrics and Electrical Insulation, vol. 20, no. 2, pp. 620627, Apr. 2013.
[7]
Y Wu, Y. Hu, Y. F. Wu, M. Z. Rong, and Q. Yi, “Investigation of an active current injection DC circuit breaker based on a magnetic induction current commutation module,”IEEE Transactions on Power Delivery, vol. 33, no. 4, pp. 18091817, Aug. 2018.
[8]
D. J. Cho, D. K. Woo, J. S. Ro, T. K. Chung, and H. K. Jung, “Novel electromagnetic actuator using a permanent magnet and an inter-locking mechanism for a magnetic switch,”IEEE Transactions on Magnetics, vol. 49, no. 5, pp. 22292232, May 2013.
[9]
Y. Sun, K. Meng, S. J. Yuan, J. L. Zhao, R. Q. Xie, Y. Yang, J. Luo, Y. Peng, S. R. Xie, and H. Y. Pu, “Modeling electromagnetic force and axial-stiffness for an electromagnetic negative-stiffness spring toward vibration isolation,”IEEE Transactions on Magnetics, vol. 55, no. 3, pp. 8000410, Mar. 2019.
[10]
J. A. Roll, B. Cheng, and X. Y. Deng, “An electromagnetic actuator for high-frequency flapping-wing micro air vehicles,”IEEE Transactions on Robotics, vol. 31, no. 2, pp. 400414, Apr. 2015.
[11]
H. Yan, Y. Liu, and L. Ma, “Mechanism of temperature’s acting on electro-hydraulic servo valve,”IEEE Access, vol. 7, pp. 8046580477, Jun. 2019.
[12]
N Ide, O. Tanaka, S. Yanabu, S. Kaneko, S. Okabe, and Y. Matsui, “Interruption characteristics of double-break vacuum circuit breakers,”IEEE Transactions on Dielectrics and Electrical Insulation, vol. 15, no. 4, pp. 10651072, Aug. 2008.
[13]
M. F. Liao, X. Y. Duan, X. Cheng, Z. H. Huang, and J. Y. Zou, “Property of 126 kV vacuum circuit breaker based on three 40.5 kV fiber-controlled vacuum interrupter modules in series,”in 2012 25th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Tomsk, 2012, pp. 2225.
[14]
Y. Y. Zhang, Y. S. Geng, L. Yu, J. Yan, Z. Y. Liu, C. M. Hu, and J. J. Yao, “Axial magnetic field strength needed for a 126 kV single break vacuum interrupter,”in 2010 24th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Braunschweig, 2010, pp. 320323.
[15]
J. M. Jiang, H. Y. Lin, and S. H. Fang, “Optimization design of a permanent magnet actuator for 126-kV vacuum circuit breaker,”IEEE Transactions on Applied Superconductivity, vol. 28, no. 3, pp. 0600105, Apr. 2018.
[16]
Z. X. Wang, L. Q. Sun, S. N. He, Y. S. Geng, and Z. Y. Liu, “A permanent magnetic actuator for 126 kV vacuum circuit breakers,”IEEE Transactions on Magnetics, vol. 50, no. 3, pp. 129135, Mar. 2014.
[17]
L. Zhang, Y. T. Zou, J. C. Yu, J. C. Qin, V. Vittal, G. Karady, D. Shi, and Z. W. Wang, “Modeling, control, and protection of modular multilevel converter-based multi-terminal HVDC systems: A review,”CSEE Journal of Power and Energy Systems, vol. 3, no. 4, pp. 340352, Dec. 2017.
[18]
H. T. Kang, Y. Liu, Q. H. Wu, and X. X. Zhou, “Switching excitation controller for enhancement of transient stability of multi-machine power systems,”CSEE Journal of Power and Energy Systems, vol. 1, no. 3, pp. 8693, Sep. 2015.
[19]
H. Nabae and T. Higuchi, “A novel electromagnetic actuator based on displacement amplification mechanism,”IEEE/ASME Transactions on Mechatronics, vol. 20, no. 4, pp. 16071615, Aug. 2015.
[20]
K. H. Hsiao, Y. Zhang, K. Shi, and J. L. Lin, “Structural analyses of mechanisms with springs in ancient China,”in 2017International Conference on Applied System Innovation (ICASI), Sapporo, 2017, pp. 11101113.
[21]
H. W. Kim, S. H. Lee, J. Y. Kim, B. T. Bae, J. H. Kim, J. S. Jang, and W. S. Yoo, “Performance improvement of spring operating mechanism for gas insulated circuit breaker by optimizing latch mechanism,” 2015in 3rd International Conference on Electric Power Equipment– Switching Technology (ICEPE-ST), Busan, 2015, pp. 410411.
[22]
B. Tang, Y. T. Xu, Q. H. Lin, and B. M. Li, “Synergy of melt-wave and electromagnetic force on the transition mechanism in electromagnetic launch,”IEEE Transactions on Plasma Science, vol. 45, no. 7, pp. 13611367, Jul. 2017.
[23]
T. Ota, Y. Mitsutake, Y. Hasegawa, K. Hirata, and T. Tanaka, “Dynamic analysis of electromagnetic impact drive mechanism using eddy current,”IEEE Transactions on Magnetics, vol. 43, no. 4, pp. 14211424, Apr. 2007.
[24]
S. L. Li, Y. J. Li, and B. Sarlioglu, “Partial irreversible demagnetization assessment of flux-switching permanent magnet machine using ferrite permanent magnet material,”IEEE Transactions on Magnetics, vol. 51, no. 7, pp. 8106209, Jul. 2015.
[25]
W. Li, A. H. Li, and H. J. Wang, “Anisotropic fracture behavior of sintered rare-earth permanent magnets,”IEEE Transactions on Magnetics, vol. 41, no. 8, pp. 23392342, Aug. 2005.
[26]
S. Hong, B. J. Bae, D. J. Cho, and H. K. Jung, “Design of electromagnetic force driving actuator (EMFA) and linkage for molded case circuit breaker,”in 2010 International Conference on Electrical Machines and Systems, Incheon, 2010, pp. 15731577.
[27]
J. H. Kang, S. H. Park, W. Y. Lee, H. K. Kim, W. B. Suh, W. S. Kim, and H. K. Jung, “Development and analysis of a new type of switchgear for high voltage gas circuit breaker: electromagnetic force driving actuator,”in 2006 12th Biennial IEEE Conference on Electromagnetic Field Computation, Miami, FL, 2006, pp. 246246.
[28]
J. H. Kang, S. Y. Kwak, R. E. Kim, and H. K. Jung, “The optimal design and dynamic characteristics analysis of electric actuator (EMFA) for 170 kV/50 kA VCB based on three-link structure,”in 2008 23rd International Symposium on Discharges and Electrical Insulation in Vacuum, Bucharest, 2008, pp. 177180.
[29]
R. E. Kim, J. H. Kang, S. Y. Kwak, and H. K. Jung, “Design of electromagnetic force driving actuator (EMFA) for molded case circuit breaker,”in 2008 International Conference on Electrical Machines and Systems, Wuhan, 2008, pp. 37463749.
[30]
Y. Liu, Q. H. Wu, H. T. Kang, and X. X. Zhou, “Switching power system stabilizer and its coordination for enhancement of multi-machine power system stability,”CSEE Journal of Power and Energy Systems, vol. 2, no. 2, pp. 98106, Jun. 2016.
[31]
M. Blank, T. Glück, A. Kugi, and H. P. Kreuter, “Digital slew rate and s-shape control for smart power switches to reduce EMI generation,”IEEE Transactions on Power Electronics, vol. 30, no. 9, pp. 51705180, Sept. 2015.
CSEE Journal of Power and Energy Systems
Pages 249-257
Cite this article:
Tian Y, Xu J, Deng Y, et al. Development and Tests of ZW-126/D2000-40 Vacuum Circuit Breakers with Controlled Switching Technology. CSEE Journal of Power and Energy Systems, 2022, 8(1): 249-257. https://doi.org/10.17775/CSEEJPES.2019.02010

1027

Views

58

Downloads

1

Crossref

N/A

Web of Science

6

Scopus

1

CSCD

Altmetrics

Received: 02 September 2019
Revised: 18 November 2019
Accepted: 25 December 2019
Published: 13 February 2020
© 2019 CSEE
Return